1. Fire Hydrant . [ ACCORD Standard ,Part 5 ]
2. Addressable fire alarm [ACCORD Standard, 5.7.2.2 ]
3. PA will be covered to all areas. [NFPA 72 -Clause 24.4.3.2.5.2 ]
4. Minimum width of aisles: Aisles shall be provided with a minimum unobstructed clear--‐width of 0.9 m (36 inc.) [ ACCORD Standard 6.5.1 ]
5. Exit Door width will be 1.15 meter(45 Inc. ),Height 2 meter (78 inc.) [BLR -2015 (54-2) ]
6. Dining facility must be provided for 15 % existing worker in the facility. [ BLR -2015 (92) ]
7. Exit will not be more distance than 50 meter from any workers. [ BLR -2015 (54-2) ]
8. Toilet facility : Male - First 100 : 1 toilet for 40 [Next 1 for 60 workers ] Female - First 100 : 1 toilet for 25 [Next 1 for 50 workers ] BLR -2015 Schedule -2 .
9. All doors in a means of egress shall be of the side--‐hinged swinging type. Roll--‐down and sliding gates and shutters shall not be allowed. [ ACCORD Standard 6.8.1 ]
10. Assembly area should be designated [ BNBC Part 4 , Sec. 4.8.11.1 ]
11. A factory having more than 3000 to 7500 workers two registered doctor , Asst. , Nurse is required . More than 7500 workers 3 registered doctor , Asst. , Nurse is required . [ BLR – 78 ]
12. Automatic sprinkler protection shall be installed throughout all portions of new and existing high--‐rise buildings with an occupiable floor greater than 23 m (75 ft) above . [ ACCORD Standard 5.3.3.]
13. Extinguishers shall be placed so that maximum travel distance to the nearest unit shall not exceed 30 m (100 ft). [ ACCORD Standard 5.6.1 ]
14. Factory Owner shall ensure that at least one trained professional individual is assigned to each factory facility to manage and monitor the operational loadings of the building. [ACCORD Standard 13.7.1.1 ]